OUTPUT POWER
CONTINUOUS
POWER
SURGE
POWER
NO LOAD
POWER
OUTPUT
VOLTAGE
OUTPUT
CURRENT
WEIGHT
LBS.
1100W 117 +/-6% 5.1 6.5
MODEL
VOLTAGE
MINIMUM
(TYPICAL)
SYSTEM
(TYPICAL)
MAXIMUM
(TYPICAL)
TYPICAL
EFFICIENCY
@ FULL
POWER
PEAK
EFFICIENCY
@ 1/3
POWER
12V
24V
32V
48V
66V
108V
10.4/10.6* 13.8V 16.5V 85% 87%
19/21V* 27.6V 33V 87% 89%
26.5/28V* 36.8V 44V 88% 90%
41.5/42.5V 55.2V 62V 87% 89%
57.5/58.5V* 75.9V 91V 88% 90%
94/95V* 125V 149V 87% 90%
INPUT POWER
*Indicates typical cut-off voltage/warning buzzer voltage
CONDITIONS
WAVEFORM
VOLTAGE OUTPUT
LINE REGULATION
LOAD REGULATION
DISTORTION
FREQUENCY
MINIMUM
-
-5%
-
-
-
-0.1%
TYPICAL
SINUSOIDAL
NOMINAL
0.1%
0.5%
1.5%
NOMINAL
MAXIMUM
-
+5%
0.5%
1%
2%
+0.1%
GENERAL
Case size (HxWxD)
125W case size= 2.16" X 4.93" X 7.90"
(2 lbs)
250W case size= 2.77" X 5.23" X 12.03"
(5 lbs)
600W case size= 3.57" X 7.69" X 12.10"
(6.5 lbs)
1100W case size= 3.57" X 7.69" X 15.05"
(10 lbs)
MECHANICAL
ENVIRONMENTAL
Temperature: -25 to 30 C full power
derated above 30 C
Humidity: 5 to 95% non condensing
Altitude: -200 to 10k feet full power,
derated above 10k
Audible Noise: Less than 45dbA
Cooling: 600W/1100W Thermo-
statically controlled
forced air. 125W/250W
convection cooled.
Finish: Painted aluminum
Warranty: Full year parts labor
*Over Voltage: Shut off at maximum input
voltage, per input conditions.
Automatic reset upon fault
correction.
*Under Voltage: Shut off at minimum input
voltage, per input conditions
*Thermal: 105 C internal temperature.
Warning buzz 5 C before
shut off
Output Short: Unit shuts off (manual reset)
*Automatically reset
PROTECTION
CIRCUITRY
XP SERIES POWER INVERTER SPECIFICATIONS
1100W 230 +/-6% 2.7 6.5
1100W**
1100W**
1100W**
600W**
250W**
250W**
250W**
125W
125W
600W**
600W**
8W
9W
6.51100W
8W
100 +/-6% 6.0
2200W
2200W
2200W
20W*
20W*
20W* 100 +/-6%
117 +/-6%
230 +/-6% 10
10
10
9.5
11.0
4.8
150W
150W
5W
5W
100 +/-6%
117 +/-6% 2
2
1.1
1.2
300W
300W
300W 6W
6W
7W
100 +/-6%
117 +/-6%
230 +/-6%
2.5
2.1
1.1
5
5
5
*10W with X2 option
**remote switchable
XP Options:
- conformal coating (07 option)
- low idle current drain (02 option)*
- circuit board with heat sink only
(04 option) many other options
available for OEM applications,
consult factory.
OPTIONS
*1100 watt only
1 1
+/- 3%
1
See www.exeltech.com for more data regarding XP Series inverters.
Page 11
7317 Jack Newell Blvd North
Fort Worth, Texas 76118-7100
817.595.4969 voice, 817.595.1290 fax
800.886.4683 toll free
e-mail address [email protected]
e-mail address [email protected]
website www.exeltech.com
TECH
Page view 10
1 2 ... 6 7 8 9 10 11 12

Comments to this Manuals

No comments