Exeltech BBS Features
Overall system features:
Integrated Inverter/charger system, designed for seamless operation together
1000 watts true sine wave inverter w/less than 2% distortion and peak efficiency
is greater than 89%
External alarm relays for remote monitoring
On battery - energizes when utilizing backup power
Low battery - energizes when batteries reach 40% remaining capacity
On time - energizes when two hours of backup have occurred
Low battery shutdown protection
LED display for all parameters
BBS status: Charge mode or BBS mode
Event counter
Accumulated Event time
External alarm relay state
Battery Capacity Meter
Battery voltage indicator
Internal or External transfer switch option
External maintenance bypass switch
Front panel multimeter test points for battery voltage measurements
Testing and certifications
Manufactured in accordance with ISO 9000/TL 9000 quality systems
Computerized calibration and testing of each system
CALTRANS compliant (JULY 2004)
Lighting/Surge rated to ANSI-C62.41 Level B2
FCC compliant to Part 15 Class A
Totally integrated system with a 20 year MTBF
Data collection, monitoring, parameter changes via RS-232 interface
BBS charger features:
Power factor corrected, 3 state battery charger
Temperature compensation
Over temperature protection for batteries (50C) halts all charging
Configurable battery parameters via RS-232
BBS Transfer Switch Features
Microprocessor controlled operation allows multi-cycle voltage calculation while
maintaining a failure detect time of less then 500 microseconds
Power conditioning maintains optimal utility voltage levels when slight variance
occur
Relay transfer time less than 10ms, optional relay less then 5ms